Key Features:
- TruAccuracyTM performance ensures the GXLdp meets its rated accuracy out of the box and is ready for installation with no additional calibration adjustments required.
- Large LCD display with backlight
- Wide selection of differential pressure ranges down to +/- 0.05 IWC
- The exclusive patented Ashcroft Spool Cal actuator provides in-place system calibration, thus adding great value when validating a process on line or calibrating the unit
- Field selectable outputs
- Two programmable switch outputs, NPN or PNP
- Adjustable display response time
- Excellent over-pressure protection
- 3-Year Warranty
- CE Mark standard
Applications:
Process Applications:
HVAC/R
Critical Environments
Building Energy Management
Comfort Control Systems
Bio-pharm
Bio-tech
Clean Room/Laboratory Pressurization
Flow Measurement
Reference Temperature
70°F ±2°F (21°C ±1°C)
Accuracy
±0.25%, ±0.5%, of span (TruAccuracy™- Terminal Point Method: includes non-linearity, hysteresis, non-repeatability, zero offset and span setting errors)
Stability
≤±0.25% span/year at reference conditions
Pressure Connection
3/16 Barbed Male
1/8 NPT Female, 1/4 Barbed Male
Pressure Ranges
Bidirectional: ±0.05 in. H₂O to ±25.00 in. H₂O (±15 Pa to ±5.00 kPa)
Unidirectional: 0.10 in. H₂O to 25.00 in. H₂O (25 Pa to 6.00 kPa)
Wetted Material
Media: Clean, dry air/gases compatible with Aluminum, Titanium, PBT, Buna, Glass, Gold, Silicone Rubber, Silicon, Silicone RTV & Brass. NOT FOR USE WITH LIQUIDS
Non-Wetted Materials
Fire-retardant ABS (Meets UL 94-V0)
Outputs
0-10 Vdc
0-5 Vdc
1-5 Vdc
1-6 Vdc
4-20 mA
Enclosure Ratings
IP67/NEMA 4
Mounting
DIN rail, wall mount, optional panel mount
Certs-Approval Filter
CE
UKCA