SIMEX SGS-12
SIMEX SGS-12 Isolators SIMEX Malaysia, Penang, Butterworth Supplier, Suppliers, Supply, Supplies | TECH IMPRO AUTOMATION SOLUTION SDN BHD
Quantity
  • isolated, self-powered isolators
  • 1 or 2 tracks
  • galvanic isolation between input/output circuits
  • 12,5 mm case
  • TS-35 DIN rail mounting
  • power supply from current loop
Description

Isolators SGS-12 series create galvanic isolation between input and output circuits. Isolator doesn’t need any power supply. 0/4-20 mA current output signal can also be processed into voltage 0/2-10V signal with standard 500Ω load resistance. Then for class 0,5% it is advised to use voltage input R ≥ 100 kΩ. Quality of isolation depends on breakdown voltage and also capacity between separated circuits.

Specification
Number of inputs
1
2
Input type
current (mA)
Input range
0/4...20 mA
Number of outputs
0
1
2
Output type
0...20 mA
4...20 mA
Galvanic isolation
2kV, 100pF
between input and output circuit
Load resistance
0...1000Ω
Power supply
current loop
21...28V DC
Protection class
IP 20
Operating temperature
-20...+60°C
Mounting
DIN rail
Case dimensions
12,5 x 99 x 114,5 mm

Please leave your enquiry here, we will reply as soon as possible.


*only support gif, jpeg, jpg, png, pdf
Switch To Desktop Version