TSURUGA MODEL 1933, 1934
TSURUGA MODEL 1933, 1934 Bargraph Meter Tsuruga Malaysia, Penang, Butterworth Supplier, Suppliers, Supply, Supplies | TECH IMPRO AUTOMATION SOLUTION SDN BHD
Quantity
  • ¡öDigital indicator in bar graph display
  • ¡ö2 points setting or 4 points settings are possible
  • ¡öScaling function is available in digital display
  •  
  • Model Designation
  • 193 ¡õ - ¡õ - ¡õ
      A   B   C
    A Setting Points
    Code Settings
    3 2 set points (H/L)
    4 4 set points (HH/H/L/LL)
    B Input
    Code Input
    1 DC 0-1 mA
    2 DC 4-20 mA
    3 DC 0-1 V
    4 DC 1-5 V
    5 DC 0-5 V
    0 Other than those above *
    *:
    Input Voltage Less than DC 10 V
    Input Current Less than DC 50 mA
    C Power Supply
    Code Power Voltage
    A AC 85-264 V
    7 DC 5 V *
    9 DC 24 V
    *:
    Terminals between power supply and input are non-isolated.

    Specifications

      1933 1934
    Bar Graph Display Display LED (Color: Red)
    Bar dots 101
    Scale length 100 mm¡¡(1.5 mm width)
    Accuracy ±(1% of FS + 1 digit)
    Response time 0.5s
    Scale plate Black Aluminum(White scale & white characters)
    Digital Display Display 0-9999¡¡LED (Color: Red)(8×4 mm)
    Scaling full scale・・・-1999 to 9999
    off set value・・・-1999 to 9999
    not available for reverse proportion to input value.
    Resolution 1/2000
    Sampling period 12 times/sec.
    Accuracy ±(0.5% of FS + 1 digit)
    Setting range H £º(set value of L + 1%)-100%
    L £º(set value of H - 1%)-0%
    HH £º(set value of H + 1%)to 100%
    H £º(set value of HH - 1%)to(set value of L + 1%)
    L £º(set value of H - 1%)to(set value of LL + 1%)
    LL £º(set value of L - 1%)to 0%
    Relay output H : 1 transfer
    L : 1 transfer
    H / L : 1 “a”contact
    HH / LL : 1 transfer *
    Hysteresis 1% of FS
    Contact capacity AC 125 V, 0.5 A
    Insulation resistance All terminals - Case¡¡DC 500 V, More than 10 MΩ
    Withstanding voltage
    Input terminals - Case AC 1500 V 1min.
    Input terminals – Power Supply terminals AC 1500 V 1min.(AC)
    Input terminals – Power Supply terminals AC 500 V 1min.(DC 24 V)
    Relay contacts – Other Circuits AC 1000 V 1min.
    Power supply AC 85-264 V¡¡50/60 Hz
    DC 24 V¡¡± 15%
    DC 5 V¡¡± 5%
    Power consumption 10 VA(AC 85-264 V)
    4 W(DC 24 V ± 15%)
    2 W(DC 5 V ± 15%)
    Operating temperature 0 to 45°C
    Storage temperature -20 to 70°C
    Weight Applox. 420 g

    * HH and H£ºCommon terminals are common, LL and L£ºCommon terminals are common

    Input Specifications

    Code Input Signal Input Impedance
    1 DC 0-1 mA 200 Ω
    2 DC 4-20 mA 10 Ω
    3 DC 0-1 V 1 MΩ
    4 DC 1-5 V
    5 DC 0-5 V
    No. 1 2 3 4 5 6 7 8 9 10 11 12
    Max. value 1 1.2 1.5 2 2.5 3 4 5 6 7.5 8 9
    Division No. 50 24 30 40 50 30 40 50 30 37.5 40 45
     

Please leave your enquiry here, we will reply as soon as possible.


*only support gif, jpeg, jpg, png, pdf