eYc THR23 Temperature & Humidity Transmitter / Indoor type
eYc THR23 Temperature & Humidity Transmitter / Indoor type Temperature & Humidity Transmitter Temperature & Humidity / Dew Point eYc Malaysia, Penang, Butterworth Supplier, Suppliers, Supply, Supplies | TECH IMPRO AUTOMATION SOLUTION SDN BHD
Quantity
Input sensor type:MEMS
Output:0 ... 10 V / 4 ... 20 mA
Accuracy(at+25°C;DC 24 V):±0.5°C / ±5%RH(30 ... 80%RH)
Measuring range:0 ... 50°C / 0 ... 100%RH(Non-condensing)
Interface:RS-485+analog
●Additional option:(ILAC/TAF)Test report-Standard calibration laboratory (TAF accreditation:3032, complying with ISO/IEC 17025)
TAF has mutual recognition arrangement with ILAC MRA

Description


●Measuring temperature and humidity
Analog outputs and RS-485
Quick easy installation and maintenance due to well designed
Cost-efficient and reliable
Data can be logged and transferred to PC via RS-485 function link free software

Specification


Display:LCD without backlight
Display readout:Double-row(Up:Humidity;Down:Temp.)
Digit:3 digits and 1 decimal
Digit height : 17.84 mm
Input sensor type:MEMS
Measuring range:0 ... 50°C / 0 ... 100%RH(Non-condensing)
Analog output:0 ... 10 V / 4 ... 20 mA
Interface:RS-485+analog
Signal connection:3-wire
Load resistance(Voltage):Voltage output:≧10 KΩ / Current output:<250 Ω
Warm-up time:<2 min;Stable time 20 min
Temp. influence:Max.-0.15%RH/℃(0°C ... 80°C)
Response time:t63(15 ... 45°C / 33 ... 75%RH)≦10 sec
Sampling time:About 3 sec
Data logger:Via RS-485 by using eYc free software
Accuracy(at+25°C;DC 24 V):±0.5°C / ±5%RH(30 ... 80%RH)
Medium:Air
Operating environment:0 ... +50°C / 0 ... 100%RH(Non-condensing)
Storage environment:-20 ... + 60°C
Power supply:DC 12 ... 36 V & AC 24 V±10%
Power consumption:DC:Max.100 mA;AC:Max.150 mA
Electrical connection:Analog & Communication:4P Connector
Installation:Indoor & Wall mount
IP rating:IP20
Electrical protection:■ Polarity protection ■ Short-circuit
Certification:CE
Housing material:PC(PC-110)(UL94V-2)
Weight:95 g

Application


Monitoring indoor environments HVAC / Air conditioning / Museums / Testing environments work places / Supermarkets / Data centers / Production wharehouses / Indoor public places to regulate the ventilation system to save energy

Please leave your enquiry here, we will reply as soon as possible.